Hotel - ibis
Checklist M – Management
existing
Responsibility for fire safety
yes
no
points
M1.1
Responsible person for fire safety nominated

existing
Fire safety register
yes
no
points
M2.1
Fire safety register available for inspection (hard copy or electronic format)

M2.2
Responsible person for the fire safety register nominated

M2.3
Fire safety register regularly updated

existing
Emergency response plan
yes
no
points
M3.1
Emergency response plan available for inspection (hard copy or electronic format)

M3.2
Responsible person for the emergency response plan nominated

M3.3
Emergency response plan regularly updated

existing
Staff fire safety training
yes
no
points
M4.1
All staff has been given appropriate information, instructions and training on appointment and a regular basis

M4.2
Staff with specific fire protection tasks (including staff present at night) has received special fire prevention training

M4.3
Training documented in the Fire Safety Register

existing
Evacuation exercise
yes
no
points
M5.1
Evacuation of the hotel described in the emergency response plan

M5.2
Basic evacuation exercise carried out on a regular basis

M5.3
Evacuation exercise documented in the Fire Safety Register

existing
Inspection and maintenance
yes
no
points
M6.1
Regular management checks performed as described in the Fire Safety Register

M6.2
Qualified persons performed inspections, tests and maintenance

M6.3
Inspections, tests and maintenance recorded in the Fire Safety Register

existing
Fire risk assessment
yes
no
points
M7.1
Fire Risk Assessment carried out regularly

M7.2
Documentation of the results of the fire risk assessment available

Remarks:
Checklist B - Building
existing
Construction & Doors
yes
no
n.rq.
points
B1.1
Individual fire compartments

B1.2
Escape routes sufficiently wide

B1.3
Escape routes protected against the ingress of fire and/or smoke

B1.4
Escape routes as short as possible to an exit door out of the building

B1.5
Persons can stay within an escape route until they reach the outside

B1.6
Blind passages kept as short as possible and protected from the effects of a fire.

B1.7
High fire risk areas separated from an escape route

B1.8
Sufficient number of staircases

B1.9
Staircases enclosed

B1.10
Skylight or window for ventilation in the upper part of the staircase

B1.11
Escape routes available at all times

B1.12
Hotel bedroom doors always be easily operable from inside

B1.13
Access doors to staircases in required quality

B1.14
Doors between staircase and basement in required quality

B1.15
Doors between bedrooms and escape routes in required quality

B1.16
Doors between areas presenting special fire hazards and escape routes in required quality

existing
Internal
yes
no
n.rq.
points
B2.1
Escape routes free from obstacles

B2.2
Escape routes free from misleading mirrors

B2.3
Operation of emergency exit doors not obstructed

B2.4
Coverings and decorations in required quality

B2.5
Emergency routes and exits requiring illumination must be provided with emergency lighting

B2.6
Escape routes adequately signposted by standard safety signs

B2.7
Assembly Point assigned

B2.8
Emergency instructions for staff & guests prominently posted in entrance hall

B2.9
A simplified layout plan on each floor

B2.10
Emergency instructions for guests prominently posted in each bedroom

B2.11
A simplified layout plan in each bedroom

Remarks:
Checklist S - Systems
existing
Lighting/ emergency lighting
yes
no
n.rq.
points
S1.1
Electric lighting system

S1.2
Electrical installation in a safe condition

S1.3
Emergency lighting system in escape routes

existing
Heating
yes
no
n.rq.
points
S2.1
Boiler room of required quality

S2.2
General shut-off device for the supply of liquid or gaseous fuel

S2.3
General shut-off device for main gas supply

S2.4
Liquefied petroleum gas in bulk stored outside

S2.5
Fixed individual heaters installed safely and maintained regularly

S2.6
Instructions for fixed individual heaters must be clearly posted.

existing
Ventilation
yes
no
n.rq.
points
S3.1
General shut-off device for ventilation

existing
Passenger and goods lifts
yes
no
n.rq.
points
S4.1
Lifts meet industry and safety standards

existing
Manual fire-fighting equipment
yes
no
n.rq.
points
S5.1
Fire-fighting equipment of required quality

S5.2
Fire-fighting equipment arranged in right place

S5.3
Fire-fighting equipment easily accessible in good working order

S5.4
Fire-fighting equipment clearly indicated

S5.5
Maintenance of fire fighting equipment

existing
Alarm and alerting
yes
no
n.rq.
points
S6.1
Acoustic alarm system of required quality

S6.2
Reliable means of alerting the emergency services

Remarks:
List E - Extras
existing
List E
yes
no
points
E1
Wireless linked smoke detection system and internal alert system in every guest room (no points if E.03 is valid)

E2
Hotel partly equipped with automatic smoke detection and alarm system (no points if E.03 is valid)

E3
Hotel fully equipped with automatic smoke detection and alarm system

E4
Maintenance for smoke & fire detection and alarm system

0
E5
Hotel partly sprinklered (no points if E.06 is valid)

E6
Hotel fully sprinklered

E7
Maintenance for sprinkler system

0
E8
Automatic notification of the fire service is possible

E9
Special measures / alarms provided for guests with are not able to react on acoustic alarms

E10
Smoke compartment in horizontal escape routes not exceeding 30 metres

E11
Smoke compartment doors are self-closing

E12
Smoke compartment doors which are held open via magnetic devices and are closed
via smoke & fire detection heads adjacent to the door

E13
Smoke compartment doors which are held open via magnetic devices can be closed via
signal from the automatic smoke & fire detection system

E14
Maintenance for smoke compartment doors

0
E15
Smoke ventilation in escape routes

E16
Smoke ventilation in stairways (no points if E.17 is valid)

E17
Positive pressure in stairways

E18
Maintenance for smoke ventilation and/or positive pressure systems

0
E19
External escape stairs

E20
Guest rooms are each fire- and smoke compartments

E21
Guest rooms separated by fire resistant walls

E22
Self closing guest room doors

E23
No basement

E24
Floors below ground floor isolated from the remainder of the stairwell by 2 doors

E25
Evacuation lifts

E26
Fire fighter lifts

E27
Fire-safety checks every 12 months

E28
Fire-safety checks every 24 months (no points if E.27 is valid)

E29
-

E30
-

E31
Fire prevention folder

E32
Use of pictograms ; posted in the entrance hall

E33
Use of pictograms ; posted in each bedroom

E34
Emergency instructions given via TV upon arrival and on demand in local language and
in appropriate foreign languages depending on the origin of the hotel's usual guests.

E35
Evacuation instructions via loudspeakers possible in local language and in appropriate foreign languages depending on the origin of the hotel's usual guests (no points if E.36 is valid)

E36
Automatic evacuation system

E37
Notification of emergency services via the European Emergency call number 112 can be dialled from every bedroom without prefix

E38
Escape hoods for every bed

E39
Additional information for guests, who need particular assistance in event of fire

E40
Local fire service attendance time within 10 minutes with at least 6 fire fighters

E41
"Guests register" with number of guests available at every time

E42
"Guests register" with number and location of guests who need assistance in the event
of a fire

E43
Running cards - Orientation cards or equal means

E44
Exit route signage at low level

E45
Fixed hose reels EN 671/1

E46
Inspection of the electrical system every 12 months by a competent person

E47
Self-extinguishing TV

E48
Written instructions for the actions to be taken by hotel staff in case of an emergency

E49
Smoking policy strictly enforced

E50
Garbage policy strictly enforced

E51
Certified fire extinguisher of the aerosol type (sprays ) available in restaurant and
kitchen

E52
Certified fire extinguisher of the aerosol type (sprays) available in guestrooms

E53
-

E54
-

E55
-

E56
-

E57
-

E58
-

E59
-

E60
-

E61
All staff has received basic instruction once

E62
All staff has received basic instruction every twelve months

E63
20% of staff has received practical fire extinguisher training once

E64
20% of staff has received practical fire extinguisher training once every 2 years

E65
Staff with specific fire protection tasks has received practical fire extinguisher training
once

E66
Staff with specific fire protection tasks has received practical fire extinguisher training
every 24 months

E67
10% of staff has received special instruction once

E68
10% of staff has received special instruction every twelve months

E69
All staff with specific fire protection tasks (including staff present at night) has received
special fire prevention training

E70
All staff with specific fire protection tasks (including staff present at night) has received
special fire prevention training every twelve months

E71
Person responsible for Fire Safety according to national standard / practice

E72
Additional Person responsible for Fire Safety according to national standard / practice

E73
Person responsible for Fire Safety according to national standard / practice refreshing
every 3 years

E74
Additional person responsible for Fire Safety according to national standard / practice
refreshing every 3 years

E75
Person responsible for Fire Safety according to national standard / practice refreshing
every 5 years

E76
Additional person responsible for Fire Safety according to national standard / practice
refreshing every 5 years

E77
Fire Safety Management Level (Advanced)

E78
Standard evacuation exercise performed every 12 months

E79
Standard evacuation exercise performed every 24 months (no points if E.78 is valid)

E80
Advanced evacuation exercise performed every 12 months

E81
Advanced evacuation exercise performed every 24 months (no points if E.80 is valid)

E82
Hotel Manager has received the F. S. hotel manager course refreshing every 5 years (no points if E.83 is valid)

E83
Hotel Manager has received the F. S. hotel manager course refreshing every 3 years

E84
Trained staff (minimum 1) available at any time on the premises (no points if E.85/E86 is valid)

E85
Trained staff (minimum 2) available at any time on the premises (no points if E.86 is valid)

E86
Trained staff (more than 2) available at any time on the premises

0
Remarks:
List C - Core requirements
existing
Alternatively
yes
no
C1.1
Hotel partly equipped with automatic smoke detection and alarm system

C1.2
Hotel fully equipped with automatic smoke detection and alarm system

existing
Additive
yes
no
C2.1
Responsible person for fire safety in the hotel designated according to national standard / practice

C2.2
Fire Safety Register containing information relating to fire safety systems, management procedures and training

C2.3
Emergency response plan

C2.4
All staff received information, instructions and training in fire safety in accordance with their duties every twelve months

C2.5
Standard evacuation exercise performed every 12 months

C2.6
All fire safety systems, e.g. smoke & fire detection and alarm system, regularly inspected and maintained by suitably qualified persons

C2.7
Regular fire risk assessment carried out, e.g. with a checklist system

C2.8
Trained staff (minimum 1) available at any time on the premises

Remarks: